Application Notes / Copley Controls / I²T Motor Overload Protection

Motor Protection

I²T Motor Overload Protection

How the I²T (amperes-squared-seconds) algorithm in Copley drives protects motors from overload, and how to set it up.

Bravo Automation Technologies is an authorized distributor of Copley Controls servo and stepper drives and serves customers in the Upper Midwest (North Dakota, South Dakota, Iowa, Missouri, Illinois, Minnesota, Indiana, Wisconsin and Michigan). Browse the Copley Controls product page.

AN-001David TormeyMarch 2002

Overview

Copley drives use an I²T (I-squared-T) algorithm to keep a motor from overheating. It sums the heat a winding takes on from current over time, so it trips on sustained overcurrent but still passes the brief peak currents a motion profile needs. That's the balance a good overload limit has to strike: catch the damage, let the transients through.

Motor Heating Fundamentals

A winding dissipates heat as the square of its current (P = I²R). Run above the continuous rating long enough and that heat degrades insulation, demagnetizes the rotor magnets, or warps parts mechanically. The I²T algorithm models this heating so the drive can act before the motor gets there.

The I²T Algorithm

The I²T value is a running estimate of accumulated heat in the motor: the integral of current squared over time. The drive watches motor current and compares that running total against the motor's thermal capacity. Below the continuous rating, the value falls to model cooling. Above it, the value climbs.

I²T = ∫(I²)dt where I is the instantaneous motor current. The algorithm compares this against the motor's rated I²T capacity to determine fault conditions.

User-Programmable Parameters

You set the protection parameters in CME 2:

  • Continuous Current Rating (Ic) - The motor's rated continuous current
  • Peak Current Limit (Ip) - Maximum allowable instantaneous current
  • I²T Limit - The motor's thermal capacity rating
  • Fault Action - Response when limit is reached (disable, fold-back, warning)

In-Limit Effect

As the I²T limit gets close, the drive can either hard-fault and disable the motor, or fold back the current limit gradually so the motor cools while it keeps running at reduced output. Fold-back is the better choice anywhere a hard stop would be worse than a slowdown.

Typical applications

  • High-duty-cycle servo applications
  • Applications with frequent acceleration/deceleration
  • Systems where motor thermal protection is critical
  • Multi-axis systems with varying load profiles